Features
- Three-Phase 340 ~ 550Vac wide range input (Dual phase operation possible)
- 110mm width
- Built-in passive PFC function compliance to EN61000-3-2
- High efficiency 94.5% and low power dissipation
- Protections: Short circuit / Overload / Over voltage / Over temperature
- Cooling by free air convection
- Built-in constant current limiting circuit
- Can be installed on DIN rail TS-35/7.5 or 15
- UL508(Industrial control equipment) approved
- EN61000-6-2(EN50082-2) industrial immunity level
- Built-in DC OK relay contact
- 100% full load burn-in test
- 3 years warranty
SPECIFICATIONS
OUTPUT
DC VOLTAGE: 24V
RATED CURRENT: 40A
CURRENT RANGE: 0 ~ 40A
RATED POWER: 960W
RIPPLE & NOISE (max.): 180mVp-p
VOLTAGE ADJUSTMENT RANGE: 24 ~ 28V
VOLTAGE TOLERANCE: ±1.0%
LINE REGULATION: ±0.5%
LOAD REGULATION: ±1.0%
SETUP, RISE TIME: 1000ms, 100ms/400VAC 800ms, 100ms/500VAC at full load
HOLD UP TIME (Typ.): 12ms / 400VAC 14ms / 500VAC at full load
INPUT
VOLTAGE RANGE: Three-Phase 340 ~ 550VAC
FREQUENCY RANGE: 47 ~ 63Hz
POWER FACTOR (Typ.): PF ≧ 0.88/400VAC PF ≧ 0.86/500VAC at full load
EFFICIENCY (Typ.): 94%
AC CURRENT (Typ.): 2A/400VAC 1.4A/500VAC
INRUSH CURRENT (Typ.): COLD START 60A
LEAKAGE CURRENT: <3.5mA / 530VAC
PROTECTION
OVERLOAD: 105 ~ 130% rated output power
Protection type: Constant current limiting, unit will shut down after 3 sec. ,re-power on to recover
OVER VOLTAGE: 29 ~ 33V
Protection type: Shut down o/p voltage, re-power on to recover
OVER TEMPERATURE: Shut down o/p voltage, recovers automatically after temperature goes down
FUNCTION
DC OK REALY CONTACT RATINGS (max.): 60Vdc/0.3A, 30Vdc/1A, 30Vac/0.5A resistive load
ENVIRONMENT
WORKING TEMP.: -30 ~ +70°C (Refer to "Derating Curve")
WORKING HUMIDITY: 20 ~ 95% RH non-condensing
STORAGE TEMP., HUMIDITY: -40 ~ +85°C, 10 ~ 95% RH non-condensing
TEMP. COEFFICIENT: ±0.03%/°C (0 ~ 50°C)
VIBRATION: Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
SAFETY & EMC
SAFETY STANDARDS: UL508 approved, EAC TP TC 004, IEC60950-1 CB approved by SIQ
WITHSTAND VOLTAGE: I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC O/P-DC OK:0.5KVAC
ISOLATION RESISTANCE: I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25℃/ 70% RH
EMC EMISSION: Compliance to EN55032 (CISPR32), EN61204-3 Class B, EN61000-3-2,-3, EAC TP TC 020
EMC IMMUNITY: Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level, criteria A, EAC TP TC 020
MTBF: 59.4K hrs min. MIL-HDBK-217F (25℃)
DIMENSIONS: (WxHxD) 110 x 125.2 x 150 mm