ioLogik W5340-HSPA-T
HSPA micro RTU controller with 4 AIs, 8 DIOs, 2 relays, -30 to 70°C operating temperature
Prodotti Correlati
Features and Benefits
- Universal tri-band UMTS/HSPA 850/1900/2100 MHz with IPSec/
- VPN support
- Definable cellular connection strategy to optimize data transmission
- Intuitive menu driven front-end intelligence
- Flexible, Unicode alarm system supporting SMS, email, SNMP Trap, TCP, UDP
- One RS-232/422/485 serial port built in to connect with field serial devices
- Backup and sustainable data logging function
- Seamless SCADA connectivity by Active OPC technology
- Configure, update firmware, and program over the air via ioAdmin
- Windows/WinCE VB/ VC.NET and Linux C APIs
- -20 to 70°C operating temperature range (T model)
Introduction
The ioLogik W5340-HSPA micro RTU controller is a rugged, compact solution for remote monitoring and alarm systems. With the ioLogik W5340-HSPA, you can define a cellular connection strategy, including Always-On and Wake-On-Demand, to optimize data transmission rates for different applications. In addition, the operational cost of cellular communication depends on the data transmission rate. With Moxa’s active technology, you can expect to cut transmission costs in half and offer different cellular connection strategies to achieve better data transmission fees. When Active OPC Server™ and DA-Center™ are used together, upon network reconnection Moxa’s ioLogik W5300 series of RTU controllers are able to transmit data logs collected offline. After each network connection, the DA-Center database gateway will compare historical data stored on the ioLogik W5300’s local SD card with its received, real-time data, and then supplement any missing data by requesting re-transmission from the RTU. For most cellular solutions, each remote modem as well as the central SCADA server is assigned static public IP when establishing bi-directional communication. Yet cellular network carriers charge higher monthly fees for static, public IPs than dynamic, private ones. Moxa’s ioLogik W5300 series and patented Active OPC Server allow users to implement dynamic IP assignments for the RTUs. The ioLogik W5300 can automatically establish communications with the Active OPC Server using a fixed IP, and the Active OPC Server™ will receive and register the ioLogik W5300’s IP address and receive or record tag updates accordingly. The ioLogik W5300 can integrate external wired clients via daisychained ioLogik E1200 I/O modules. ioLogik E1200 modules support simple daisy chaining and cost-free peer-to-peer I/O extensions. Through the RJ45 Ethernet port, the ioLogik W5300 can support up to three connected ioLogik E1200 series I/O modules to enforce a flexible and scalable network expansion that best fits customers’ needs.
Inputs and Outputs
Analog Inputs: 4 channels
Configurable DI/Os: 8 channels
Relay Outputs: 2 channels
Isolation: 3k VDC or 2k Vrms
Analog Input
Type: Differential input
Resolution: 16 bits
I/O Mode: Voltage / Current
Input Range: 0 to 10 V, ±10 V, ±5 V, 0 to 20 mA, 4 to 20 mA
Accuracy:
±0.1% FSR @ 25°C
±0.3% FSR @ -30 and 70°C
Sampling Rate:
All channels: 32 samples/sec
Per channel: 8 samples/sec
Single channel: 100 samples/sec
Input Impedance: 200k ohms (min.)
Built-in Resistor for Current Input: 120 ohms
Digital Input
Sensor Type: Wet Contact (NPN or PNP) and Dry Contact
I/O Mode: DI or Event Counter
Dry Contact:
On: short to GND
Off: open
Wet Contact (DI to GND):
On: 0 to 3 VDC
Off: 10 to 30 VDC
Common Type: 4 points per COM
Counter Frequency: 900 Hz, power off storage
Digital Filtering Time Interval: Software Configurable
Digital Output
Type: Sink
I/O Mode: DO or Pulse Output
Pulse Output Frequency: 1 kHz
Over-voltage Protection: 45 VDC
Over-current Protection: 2.6 A (4 channels @ 650 mA)
Over-temperature Shutdown: 160°C (min.)
Current Rating: 200 mA per channel
DIO Output Leakage Current: 3.6 mA @ 24 VDC
Relay Output
Type: Form A (N.O.) power relay
Contact Current Rating: Resistive Load: 1 A @ 30 VDC, 250 VAC, 110 VAC
Initial Insulation Resistance: 1000 m ohms (min.) @ 500 VDC
Mechanical endurance: 5,000,000 operations
Electrical endurance: 600,000 operations @ 1 A resistive load
Contact Resistance: 100 m ohms (max.)
Pulse Output: 0.3 Hz at rated load
Power Requirements
Power Consumption:
Always on: 196 mA @ 24 VDC
On demand: 189 mA @ 24 VDC
MTBF (mean time between failures)
Time: 280,739 hrs
Database: Telcordia (Bellcore)
Computer
CPU: ARM9 based CPU, 32-bit/160 MHz
SDRAM/Flash: 2 MB
Storage
Expansion Slot: Up to 32 GB SD™ memory card (SD 2.0 compatible)
Note: For units operating in extreme temperatures, industrial grade, wide-temperature SD cards are required.
Cellular
Network: Five band UMTS/HSPA+ 800/850/AWS/1900/2100 MHz
Internet:
HSPA+:
Up to 5.76 Mbps upload speed.
Up to 14.4 Mbps download speed.
UMTS: Up to 384k bps upload/download speed.
GPRS/EDGE:
Multi-slot class: Class 12
Coding schemes: CS1 to CS4
Terminal device class: Class B
SMS: Point-to-Point Text/PDU mode
SIM Control Voltage: 3 V / 1.8 V
LAN
Ethernet: 1 10/100 Mbps RJ45 port
Protection: 1.5 kV magnetic isolation
Protocols: Modbus/TCP, TCP/IP, UDP, DHCP, BOOTP, SNMP, SNTP
Serial Communication
Interface: 1 x RS-232/422/485, software selectable(9-pin D-Sub male, or 5-contact terminal block)
Baudrate: 300, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 bps
Power Requirements
Power Input: 24 VDC nominal, 12 to 36 VDC
Physical Characteristics
Dimensions: 46.8 x 135 x 105 mm (1.84 x 5.31 x 4.13 in)
Weight: 495 g
Mounting: DIN rail (standard), wall (optional)
Environmental Limits
Operating Temperature:
Standard Models: -10 to 55°C (14 to 131°F)
Wide Temp. Models: -30 to 70°C (-22 to 158°F)
Storage Temperature: -40 to 85°C (-40 to 185°F)
Ambient Relative Humidity: 5 to 95% (non-condensing)
Altitude: Up to 2000 m
Standards and Certifications
Safety: UL 508, EN 60950-1, NCC
EMI: EN 55022; EN 61000-3-2; EN 61000-3-3;
FCC Part 15, Subpart B, Class A
EMS: EN 55024, EN 61000-4-2, EN 61000-4-3,EN 61000-4-4, EN 61000-4-5, EN 61000-4-6,
EN 61000-4-8, EN 61000-4-11, EN 61000-6-2
Shock: IEC 60068-2-27
Freefall: IEC 60068-2-32
Vibration: IEC 60068-2-6
Green Product: RoHS, CRoHS, WEEE
Warranty
Warranty Period: 2 years*
*Note: Because of the limited lifetime of power relays, products that use that component are covered by a 2-year warranty.